Allowable current for a repeted service, for a lasting period of 5 min.
Cross sectional conductor area
Allowable current for a specified percentage of the charging time
100%
85%
80%
60%
35%
20%
8%
mmq
Ampère
Ampère
Ampère
Ampère
Ampère
Ampère
Ampère
10
100
101
102
106
119
143
206
16
135
138
140
148
173
212
314
25
180
186
189
204
244
305
460
35
225
235
239
260
317
400
608
50
285
299
305
336
415
529
811
70
355
375
383
426
531
682
1053
95
430
456
467
523
658
850
1319
120
500
532
545
613
776
1006
1565
150
580
619
634
716
911
1184
1845
185
665
711
729
826
1054
1374
2145
Allowable current for a repeted service, for a lasting period of 10 min.
Cross sectional conductor area
Allowable current for a specified percentage of the charging time
100%
85%
80%
60%
35%
20%
8%
mmq
Ampère
Ampère
Ampère
Ampère
Ampère
Ampère
Ampère
10
100
100
100
101
106
118
158
16
135
136
136
139
150
174
243
25
180
182
183
190
213
254
366
35
225
229
231
243
279
338
497
50
285
293
296
316
371
457
681
70
355
367
373
403
482
602
908
95
430
448
456
498
606
765
1164
120
500
524
534
587
721
917
1404
150
580
610
622
689
853
1090
1676
185
665
702
717
797
995
1277
1971

Technical Standard CEI UNEL 00722 - Tables 1 & 2 included

Le anime dei cavi multipolari devono essere identificate mediante I colori indicati nelle tabelle 1 e 2



Cavi con anima giallo-verde (Tab.1)
Sezione
Nominale del conduttore di rame
Colore delle anime
Conduttori di fase/neutro
Conduttore di protezione
Neutro
Fase
Fase
Fase
3
Giallo/Verde
Blu
Marrone
/
/
4
Giallo/Verde
Blu
Marrone
Nero
/
5
Giallo/Verde
Blu
Marrone
Nero
Grigio
Allowable current for the service of one cycle, for a lasting period of 5 min.
Cross sectional conductor area
Allowable current for a specified percentage of the charging time
100%
85%
60%
35%
mmq
Ampère
Ampère
Ampère
Ampère
10
100
103
108
122
16
135
145
175
230
25
180
195
230
300
35
225
245
290
375
50
285
305
365
480
70
355
385
460
600
95
430
470
560
730
120
500
540
650
850
150
580
630
750
980
185
665
720
860
1120

Technical Standard CEI 20-40 - tables from 8 to 11 included

Allowable current and drop voltage for arc welding cables



Cavi senza anima giallo-verde (Tab.2)
Sezione
Nominale del conduttore di rame
Colore delle anime
Conduttori di fase/neutro
Neutro
Fase
Fase
Fase
Fase
2
Blu
Marrone
/
/
/
3
Blu
Marrone
Nero
Grigio
/
4
Blu
Marrone
Nero
Grigio
/
5
Blu
Marrone
Nero
Grigio
Nero